Rack Power Distribution Unit — AP7610Product Description and InventoryDescriptionThe AP7610 Rack PDU mounts horizontally in any standard 19-inch EIA-3
Rack PDU Configuration10 Rack Power Distribution Unit — AP7610Rack PDU Configuration optionRack PDU Configuration, main menu option 2, provides the fo
Rack PDU ConfigurationRack Power Distribution Unit — AP7610 11To change as setting:1. Type 1, and press ENTER to move the arrow cursor to the next set
12 Rack Power Distribution Unit — AP7610How to Download Firmware to a Rack PDU1. Go to www.apc.com/tools/download/ to see if there is a more recent fi
Rack Power Distribution Unit — AP7610 13SpecificationsAP7610Electrical Input connector NEMA L21-20 plugOutput connectors Three NEMA L5-20 outlet; Thre
Radio Frequency InterferenceThis equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of th
*990-1474*APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the following ways:• Vi
Product Description and Inventory2 Rack Power Distribution Unit — AP7610AP7610-compatible Rack PDUsThe AP7610 Metered Rack PDU requires connection to
Rack Power Distribution Unit — AP7610 3Safety and GroundingRead the following information before installing or operating your APC AP7610 Rack PDU:• Th
4 Rack Power Distribution Unit — AP7610How to Install the PDUOverviewInstall the AP7610 Rack PDU in the rear, top two U-spaces of a rack or enclosure
How to Install the PDURack Power Distribution Unit — AP7610 51. Insert caged nuts (provided with the enclosure) on the vertical mounting rails above a
6 Rack Power Distribution Unit — AP7610OperationDisplay interfaceControl button:• Press to change the phase of the current displayed on the digital d
OperationRack Power Distribution Unit — AP7610 7Rear of AP7610Alarm conditionsConfigure warning and alarm limits through the internal menus, using a s
8 Rack Power Distribution Unit — AP7610Rack PDU ConfigurationHow to configure through a serial port connection1. Connect an available serial port on y
Rack PDU ConfigurationRack Power Distribution Unit — AP7610 9Using the menusTo view a menu, type the associated number and press ENTER.Users can view